Multimeter with Temperature and Microamps HVAC
Reference | FLUKE-116EUR |
---|---|
EAN code | 02025680161375 |
Manufacturer | FLUKE |
Brand | FLUKE |
Promotion valid untill | Dec 31, 2023 |
Data sheet | FLUKE-116.pdf |
Technical sheet | FLUKE-110-series.pdf |
While stocks last | No |
Fluke 116 Multimeter - HVAC
The ideal multimeter for HVAC technicians
The Fluke 116 Multimeter is specifically designed for heating, ventilation, and air conditioning equipment installers (HVAC technicians). This measuring instrument allows for quick and efficient detection of HVAC problems.
Temperature and microampere measurement
The Fluke 116 Multimeter features advanced measurement functions, including temperature and microampere measurement ranges. This allows for accurate temperature measurement and detection of microamperes, which is essential for identifying HVAC problems.
Efficient and reliable
With the Fluke 116 Multimeter, you can perform measurements quickly and reliably. Thanks to its user-friendly interface and clear measurement results, you can work efficiently and make accurate diagnoses.
Useful features:
- Digital multimeter designed specifically for HVAC professionals
- Includes built-in thermometer to measure temperature from -40°C to z400°C (-40°F to 752°F)
- Provides microamps to test flame sensors
- Features low input impedance to helps prevent false readings due to ghost voltage
- Presents a large white LED backlight for working in poorly lit areas
- Measures resistance, continuity, frequency, and capacitance
- Provides Min/Max/Average to record signal fluctuations
- Comes with a holster with probe holders for easy storage
- Features a compact ergonomic design for one-handed operation
- Fits into optional ToolPak™ magnetic hanger for hands-free operation
- CAT III 600 V safety rated"" For HVAC technicians, building maintenance
Includes:
- 4 mm silicone test lead set
- 80BK Integrated Temperature probe
- Holster
- Installed 9 V battery
- User manual
Specifications: Fluke 116 HVAC Multimeter with Temperature and Microamps
Specifications | ||
Maximum voltage between any terminal and earth ground | 600 V | |
Safety | IEC 61010-1: Pollution Degree 2 IEC 61010-2-033: CAT III 600V |
|
Display | Digital: 6,000 counts, updates 4 per second | |
Bar graph | 33 segments, updates 32 per second | |
Operating temperature | -10°C to + 50°C | |
Storage temperature | -40°C to + 60°C | |
Battery type | 9 volt Alkaline, IEC 6LR61 | |
Battery life | 400 hours typical, without backlight | |
Accuracy Specifications | ||
DC millivolts | Range/resolution | 600.0 mV / 0.1 mV |
Accuracy | ±([% of reading] + [counts]): 0.5% + 2 | |
DC volts | Range/resolution | 6.000 V / 0.001 V 60.00 V / 0.01 V 600.00 V / 0.1 V |
Accuracy | ±([% of reading] + [counts]): 0.5% + 2 | |
Auto volts | Range/resolution | 600.0 V / 0.1 V |
Accuracy | 2.0% + 3 (DC, 45 Hz to 500 Hz) 4.0% + 3 (500 Hz to 1 kHz) |
|
AC millivolts1 True RMS | Range/resolution | 600.0 mV / 0.1 mV |
Accuracy | 1.0% + 3 (DC, 45 Hz to 500 Hz) 2.0% + 3 (500 Hz to 1 kHz) |
|
AC volts1 True RMS | Range/resolution | 6.000 V / 0.001 V 60.00 V / 0.01 V 600.0 V / 0.1 V |
Accuracy | 1.0% + 3 (DC, 45 Hz to 500 Hz) 2.0% + 3 (500 Hz to 1 kHz) |
|
Continuity | Range/resolution | 600 Ω / 1 Ω |
Accuracy | Beeper on < 20 Ω, off > 250 Ω detects opens or shorts of 500 μs or longer. |
|
Ohms | Range/resolution | 600.0 Ω / 0.1 Ω 6.000 kΩ / 0.001 kΩ 60.00 kΩ / 0.01 kΩ 600.0 kΩ / 0.1 kΩ 6.000 MΩ / 0.001 MΩ |
Accuracy | 0.9% + 1 | |
Range/Resolution | 40.00 MΩ / 0.01 MΩ | |
Accuracy | 5% + 2 | |
Diode Test | Range/resolution | 2.00 V / 0.001 V |
Accuracy | 0.9% + 2 | |
Capacitance | Range/resolution | 1000 nF / 1 nF 10.00 μF / 0.01 μF 100.0 μF / 0.1 μF 9999 μF / 1 μF 100 μF to 1000 μF |
Accuracy | 1.9% + 2 | |
Range/resolution | > 1000 μF | |
Accuracy | 5% + 20% | |
Lo-Z Capacitance | Range | 1 nF to 500 μF |
Accuracy | 10% + 2 typical | |
Temperature² (Type-K thermocouple) |
Range/resolution | -40°C to 400°C / 0.1°C |
Accuracy | 1% + 10² | |
Range/resolution | -40°F to 752°F / 0.2°F | |
Accuracy | 1% + 18² | |
AC μA true-rms (45 Hz to 500 Hz) | Range/resolution | 600.0 μA / 0.1 μA |
Accuracy | 1.5% + 3 | |
DC μamps | Range/resolution | 600.0 μA / 0.1 μA |
Accuracy | 1.0% + 2 | |
Hz (V or A input)² | Range/resolution | 99.99 Hz / 0.01 Hz 999.9 Hz / 0.1 Hz 9.999 kHz / 0.001 Hz 50.00 kHz / 0.01 Hz |
Accuracy | 0.1% + 2 | |
1. All AC voltage ranges except Auto-V/LoZ are specified from 1% to 100% of range. Auto-V/LoZ is specified from 0.0 V. 2. Temperature uncertainty (accuracy) does not include the error of the thermocouple probe. 3. Frequency is AC coupled, 5 Hz to 50 kHz for AC voltage. Frequency is DC coupled, 45 Hz to 5 kHz for AC current. 4. Temperature Range/Resolution: -40°F to 752°F / 0.2°F. |
||
Mechanical and General Specifications | ||
Size | 167 x 84 x 46 mm (6.57 x 3.31 x 1.82 in) | |
Weight | 550 g | |
Warranty | 3 years |
* Ondanks een zeer uitgebreid stocksysteem, is het mogelijk dat de voorraadstatus niet overeenstemt met de actuele voorraad. Aarzel niet ons te contacteren, indien u zekerheid wenst over de beschikbaarheid.
** De weergegeven foto bij de producten kan verschillen van het eigenlijke product.